Boiler Gasket
Installation Instructions
- Remove old gasket
and thoroughly clean cover plate flange, ring, or shell gasket surfaces.
- Position Blue-Max®
gasket on cover plate. Please make sure the gasket is pushed down tight
and flat around shoulder. Note: If shoulder of plate is rounded making
the gasket hard to keep in place, use Blue-Max®
Sta-Ons®. (Do not use any
grease, sealant, or lubricants.) This will ensure that one side
of the gasket does not slide back up onto the shoulder during installation
causing only the inner edge of the ring or shell to catch only the outer
edge of the gasket causing premature failure when pressure builds.
- Install cover plate
into opening, set crab/s, tighten nut/s finger tight while making sure
the inside diameter of the gasket is centered evenly around the inside
edge of the ring or shell.
Note: If the cover plate is too small for the opening in the boiler,
it's easy to place the cover off center. An off center plate will cause
the same occurrence as previously described in the above note (2).
- Tighten nut/s with
wrench a full turn. When all gaskets are in place as previously described,
torque style #810-T handhole gasket sizes to 90-ft. lbs., and style
#800-T manhole gasket sizes to 120-ft. lbs.
Note: All plates with double crabs should be alternately tightened
( ie).: 40 / 80 / 120-ft. lbs.
- Fill and fire boiler.
Note: Should gaskets leak while filling boiler do not tighten nut/s.
The soft rubber compound under the PTFE cures up with heat allowing
the rubber to fill into the pits and irregular sealing surfaces. During
this curing process it is not uncommon for leakage to occur.
- Once the boiler
has come up to operating temperature and pressure, allow the boiler
to operate for four hours. After this period, retighten any leaking
gaskets only enough to stop leakage.
- Extra care should
be taken when installing gaskets on the bottom of a boiler shell. Small
particles of scale or sand tend to run down on the mating surface between
the time the surface is cleaned and the cover plate is put in place
ready to be torqued.
- Blue-Max®
boiler gaskets are sold and intended for use on steam boilers.
Performance
data for the Blue-Max® boiler
gaskets have been developed from field-testing, customer field reports
and or in-house testing. While the utmost care has been used in compiling
this information, we can assume no responsibility for errors.
Specifications subject to change without notice.
Blue-Max®
is a registered trademark of O.G. Supply, Inc. for: gaskets for steam
boilers, steam generators and water heaters in class 17(U.S. CL.35).
Registered Jan. 31st 1989. Reg. No. 1,522,622 O.G. Supply, Inc.
All rights reserved. .This installation information cancels all previous
issues.
Subject to change without notice. BMBGII 01-22-0
|
|